Figure 6-26 Setting SNMP port
NO TE
SNMP Port is set to 161 by default.
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1. Tap Add under SNMP Trap.
2. Set Trap Address as planned and Trap Port to the actual port number.
NO TE
Trap Port is set to null by default.
3. Select the SNMP Version. If a SNMPv3 user is congured, it is recommended
that SNMP Version be set to SNMPv3.
4. If SNMP Version is set to SNMPv3, select a SNMPv3 user name, and then
tap as shown in Figure 6-27.
Figure 6-27 Setting SNMP trap parameters
5. Tap Submit under SNMP Trap.
----End
Follow-up Procedure
After a USB ash drive has been inserted into the controller USB port and
successfully identied, tap Export File under MIB File to export the MIB le to the
USB
ash drive for the customer's use in accessing a third-party EMS. Figure 6-28
shows successful le export.