Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the front door, and remove the water pan cover, as shown in Figure 11-32.
Figure 11-32 Removing a water pan cover
Step 3 Cut the cable tie securing the liquid level detector and remove the terminal.
Step 4 Remove the two buttery nuts on the liquid level detector fastener, remove cables
from the liquid level detector, and remove the liquid level detector and its fastener,
as shown in Figure 11-33.
NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual 11 Parts Replacement
Issue 08 (2021-09-17) Copyright © Huawei Technologies Co., Ltd. 277