Checking the high pressure adapter
In the high pressure adapter there is a 400 µm strainer to protect the flow
control valve. Clean this strainer at least every six months, or more frequently
if heavy soiling makes it necessary.
The flow rate through the high-pressure adapter is limited to approx.
0.55 to 0.7 l/min.
If the necessary flow rate is not reached, you must check and clean the
strainer in the adapter, refer to page 97.
FCU1310
en(us)
Page 96 / 124
BeWa FCU1310 V300 3371346f en-us 2017-01-27.docx 2017-01-27