Section 5 - Commissioning
COMMISSIONING
74 Installation and Maintenance
5.8.9.9.5 For serviceman, Test, DHW running
Press O to return to the menu.
DHW running is on.
OK
Tw_out 15C
T5 15C
DHW running

temperature and T5 (Cylinder) temperature..
5.8.9.10 For serviceman, Special function
To set a parameter scroll through the settings, use and
. Press O to select the parameter.
Preheating for floor
Floor drying up
Special function
- 5.8.9.10.1
- For Floor drying up settings, refer to 5.8.9.10.2
5.8.9.10.1 For serviceman, Special function, Preheating for oor
Preheating for floor
Preheating for floor
T1S
30C
72hours
_ _
t_ARSTH
Elapsed time
T1S
(default 15° C)
T_ARSTH
(default 72 hours)
Elapsed time is the amount of time that the

Tw-out temp.
Preheating for floor
T1S
t_ARSTH
72hours
15C
_ _
0C
Elapsed time
Tw_out temp.
 and until
 is illuminated. Then press O.

and
until T1S illuminated. Then press O to access the parameter.
Then use
and to change.
 and until t_
ARSTH illuminated. Then press O to access the parameter.
Then use and to change.
Elapsed time 
function has been running for.
Tw-out temp.
5.8.9.10.2 For serviceman, Special function, Floor drying up
Floor drying up
FLoor drying up
t_Dryup
8days
5days
5days
t_Highpeak
t_Drydown
t-Dryup

(default 8 days)
t-Highpeak
heating drying temperature is maintained for.
(default 5 days)
t-Drydown

to OFF.
(default 5 days)