Section 5 - Commissioning
COMMISSIONING
83
Installation and Maintenance
t_IBH_DELAY (not applicable to this appliance) 30 minutes
T4_IBH_ON (not applicable to this appliance) -5°C
P_IBH1 (not applicable to this appliance) 0.0kW
P_IBH2 (not applicable to this appliance) 0.0kW
AHS FUNCTION
(AHS = Additional Heat Source, ie Boiler)
NO / HEATING & DHW / HEATING
NO (Disabled)
AHS _PUMPICONTROL
RUN / NOT RUN
RUN
 5°C
t-AHS_DELAY (delay between heat pump on and boiler on) 30 minutes
Other heat source
T4_AHS_ON
(change to +2°C for hybrid)
(>2°C heat pump on, <2°C boiler on)
-5°C
EnSwitchPDC (YES / NO) NO (Disabled)
GAS-COST £0.85/m3
ELE-COST £0.20/kWh
MAX-SETHEATER (Not applicable) 80°C
MIN-SETHEATER (Not applicable) 30°C
MAX-SIGHEATER (not applicable to this appliance) 10V
MIN-SIGHEATER (not applicable to this appliance) 3V
TBH FUNCTION
(TBH = Tank Booster Function)
(YES / NO)
NO (Disabled)
dT5_TBH_OFF (not applicable to this appliance) 5°C
t_TBH_DELAY (not applicable to this appliance) 30 minutes
T4_TBH_ON (not applicable to this appliance) 5°C
P_TBH (not applicable to this appliance) 3kW
Solar function (not applicable to this appliance) NO (Disabled)
Solar control (not applicable to this appliance) NO (Tsolar)
Deltatsol (not applicable to this appliance) 10°C
Holiday
away
setting
 25°C
 25°C
Serviceman,
Service Call
Phone number 000000000000000
Mobile number 000000000000000
Serviceman,
Restore factory
settings
Restore factory settings No
Serviceman, Test
Run, Point Check
SV2 (not applicable to this appliance) Auto
SV3 (not applicable to this appliance) Auto
Pump_I (Primary circulation pump) Auto
Pump_O (CH Zone 1 pump) Auto
Serviceman, Test
run,
Air purge
Air Purge (runs pump to extract air from system) 󰀨
Air purge Pump_I output 70%
Air purge running time 20min
 1.70m3/h
Serviceman, Test
run
Circulated pump running (Primary circulation pump) Auto
Heating running Auto
DHW running Auto
Special
function
 OFF (disabled)
 15°C
 72 hours
 OFF (disabled)
T_Dryup (Floor drying up, time to increase temperature to maximum 8 days
T_Highpeak (Floor drying up, time at maximum temperature) 5 days
T_Drydown (Floor drying up, time to decrease temperature to ambient) 5 days
t-Drypeak (Floor drying up, maximum temperature) 45°C
Start time (Floor drying up, start time) 00:00
Start date (Floor drying up, start date)
Current
date+1