Section 5 - Commissioning
COMMISSIONING
84 Installation and Maintenance
Auto
restart
Auto restart cooling/heating mode (enable/disable heating after mains interruption) 1 (Enabled)
Auto restart DHW mode (enable/disable DHW after mains interruption) 1 (Enabled)
Power
input
limitation
Power input limitation (limits power drawn by appliance, not applicable) 1

M1 M2 (not applicable to this appliance) 󰀨
Smart grid (not applicable to this appliance) NO (Disabled)
T1T2 (not applicable to this appliance) NO (Disabled)
Tbt (not applicable to this appliance) NO (Disabled)
P_X PORT (not applicable to this appliance) NO (Defrost)
Cascade
setting
PER_START (Maximum output of appliance at cascade start up) 10%
TIME_ADJUST (Time at which additional units added/removed from cascade) 5 minutes
HMI
address
setting
HMI setting
(0 allows all parameters to be changed)
(1 limits changes to Room Stat functions)
(should be left at 0)
0 (Master)
HMI address for BMS (not applicable to this appliance) 1
Stop BIT (not applicable to this appliance) 1 (Stop bit 1)
Common
setting
t_DELAY PUMP (Primary circulation pump overrun time) 2.0 minutes
t1_ANTILOCK PUMP (pump non operation time before anti-sieze occurs) 24 hours
t2_ANTILOCK PUMP RUN (Pump anti-sieze run time) 60 seconds
t1-ANTILOCK SV (3-way valve non operation time before anti-sieze occurs) 24 hours
t2-ANTILOCK SV RUN (3-way valve anti-sieze run time) 30 seconds
Ta-adj. (not applicable for this appliance -2°C
PUMP_I SILENT OUTPUT (not applicable fo this appliance) 100%
Energy metering (not applicable to this appliance) NO (Enabled)
Pump_0
(ON and AUTO)
AUTO (controlled by demand)