IDEC SmartRelay functions
IDEC SmartRelay Manual 192
4.4.20 Analog amplifier
Short description
This special function amplifies the value of an analog input
and outputs the result at an analog output.
*AI1...AI8:0...10 V corresponds with 0...1000 (internal value).
Gain and offset parameters
Please note the information on gain and offset parameters in
Chapter
4.3.6.
Parameter p (number of decimals)
Applies only to the AQ value in a message text.
Symbol in
IDEC
SmartRelay
Wiring Description
Input Ax You apply the analog signal to
be amplified at input Ax.
Use the analog inputs AI1...AI8
(
*
)
, the Analog Memory Markers
AM1...AM6, the block number of
a function with analog output.
Parameter A: Gain
Range of values:
±10.00
B: Offset
Range of values:
±10,000
p: Number of decimals
Range of values:
0, 1, 2, 3
Output AQ This special function has an an-
alog output! This output can only
be connected with the analog in-
put of a function or with an Ana-
log Memory Marker.
Range of values for AQ:
-32768...+32767
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC SmartRelay FL1D Series and is the answer not in the manual?

IDEC SmartRelay FL1D Series Specifications

General IconGeneral
BrandIDEC
ModelSmartRelay FL1D Series
CategoryControl Unit
LanguageEnglish

Related product manuals