IDEC SmartRelay functions
IDEC SmartRelay Manual 198
Depending on your configuration, either input R takes priority
over input S (i.e. input S is not effective when R = 1), or vice
versa (i.e. input R is not effective when S = 1).
After a power failure, the current impulse relay and output Q
are reset if you have not enabled retentivity.
View in programming mode:
B29 R
Par=RS
B29 R
Par=SR
Press
or
This special function is not available in parameter assign-
ment mode.
Note
If Trg = 0 and Par = RS, the special function “Current impulse relay”
corresponds with the special function “Latching relay” (see Chapter
4.4.21).