IDEC SmartRelay functions
IDEC SmartRelay Manual 218
Parameter L1 (Level 1) and L2 (Level 2):
Levels to be reached
Range of values for
each level:
–10,000 to +20,000
MaxL:
Maximum value that must
not be exceeded under
any circumstances.
Range of values:
–10,000 to +20,000
StSp:
Start/Stop offset: value
that is added to Offset(B)
to create the start/stop lev-
el.If the Start/Stop offset is
0, then the start/stop level
is Offset(B).
Range of values:
–10,000 to +20,000
Rate:
Acceleration with which
level 1, level 2 or Offset is
reached.
Steps/seconds are issued.
Range of values:
1 to 10,000
A: Gain
Range of values:
0 to 10.00
B: Offset
Range of values:
±10,000
p: Number of decimals
Range of values:
0, 1, 2, 3