102
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
List of t family parameters.
To enter in the parameters of the family t, press "MODE" with t on the display. "t." will appear.
Press "INFO" to scroll the submenus of the t family.
Id
Parameter
Parameter Description Range Default
Value
customized
t.0
Central heating
set point
minimum
temperature
Set minimum central heating / C.H. set limit available
20..(t.1-5)
(20-50)
20
t.1
Central heating
set point
maximum
temperature
Set maximum central heating / C.H. set limit available
(t.0+5)..85
(25-85)
85
t.2
Boost Mode
(DHW
Recirculation
Function Par.
2.4)
0: Always o
1: Always ON
2: Auto
- -
t.3
Solar Delay
timing
Not used - -
t.4
Domestic hot
water priority
timer
Not used - -
t.5
Central heating
ignitions timer
e boiler has an electronic timer, which prevents the burner
from igniting too oen in central heating mode.
0-600 seconds 180
t.6
Heating ramp
timing
In central heating mode, the boiler performs an ignition
ramp in order to reach the maximum output set.
0-840 seconds 180
t.7
Heating
switch-on delay
request from
room thermo-
stat or remote
control
e boiler is set to switch-on immediately aer a request.
In the event of particular systems (e.g. area systems with
motorised thermostatic valves etc.) it may be necessary to
delay ignition.
0-600 seconds 0
t.8 Display lighting
Establishes the display lighting mode.
0: the display lights up during use and lowers aer 15 seconds
of inactivity. In the case of anomaly the display remains at
maximum lighting.
1: display lighting always low.
2: display lighting always high.
0-2 0