INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
MODEINFORESET
+
-
+
-
63
Once in the menu, press INFO until the ashing "tM" appears.
Conrm by pressing MODE.
MODEINFORESET
+
-
+
-
64
Once the function is activated, the service symbol (
) will start
ashing. e digits on the le will display "tM" while those on the
right will display the ow temperature alternating with the indi-
cation (MA, AC, Mi) of the current phase.
e ashing (
) or ( ) symbols indicate on which circuit the
energy produced during calibration is being dissipated.
Once the boiler is switched on, the symbol (
) will appear ash-
ing.
Pressing the Reset button allows you to exit the function in ad-
vance.
MODEINFORESET
+
-
+
-
65
Once the system has stabilised and reached the ame set for the
current phase, the symbol (
) becomes xed and "0" appears on
the right digit.
Under these conditions, the combustion value (CO
2
) related to the delivery of maximum rated power (MA), intermediate igni-
tion (Ac) and minimum ignition (Mi) can be measured