97
INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
List of G family parameters.
To enter in the parameters of the family G, press "MODE" with G on the display. "G." will appear.
Press "INFO" to scroll the submenus of the G family.
Victrix Extra 12 Plus
Id
Parameter
Parameter Description Range Default
Customised
value
G. Gas type Display gas type: nG (Methane) or LG (LPG) nG-LG-AP nG
n. Boiler model Dene the boiler model 0-20* 3
S.0
Minimum no. of
fan revs
Denes the operating speed of the fan at minimum output 700-3000 1650
S.1
Maximum no. of
fan revs
Denes the operating speed of the fan at maximum output 2000-8300 3525
S.2
Ignition phase
no. of fan revs
Denes the operating speed of the fan during the ignition
phase
2000-4500 3800
F.0 Flue length Denes the length of the ue (Parag. 3.12) 0-2 0
F.1
Presence of
clapet valve on
ue gas (C
(10)
-
C
(12)
)
If present, automatic corrections are made to the fan's
operating range
0-1 0
* : 0 cannot be used; from 4 to 20 cannot be used; only 1-2-3 available.
Victrix Extra 24 Plus
Id
Parameter
Parameter Description Range Default
Customised
value
G. Gas type Display gas type: nG (Methane) or LG (LPG) nG-LG-AP nG
n. Boiler model Dene the boiler model 0-20* 1
S.0
Minimum no. of
fan revs
Denes the operating speed of the fan at minimum output 700-3000 2200
S.1
Maximum no. of
fan revs
Denes the operating speed of the fan at maximum output 2000-8300 6350
S.2
Ignition phase
no. of fan revs
Denes the operating speed of the fan during the ignition
phase
2000-4500 3800
F.0 Flue length Denes the length of the ue (Parag. 3.12) 0-2 0
F.1
Presence of
clapet valve on
ue gas (C
(10)
-
C
(12)
)
If present, automatic corrections are made to the fan's
operating range
0-1 0
* : 0 cannot be used; from 4 to 20 cannot be used; only 1-2-3 available.