INFICON Warning and error messages | 7
UL3000-Fab-ULTRA-Operating-instructions-iinb73en1-09-(2109) 97 / 152
Type Notification Possible sources of
error
Remedy
W110 Real-time clock was reset!
Enter date and time
The real-time clock has
not been set
Enter the correct date and time
Check that the message does not appear
when you restart the device
Battery jumper on the
MSB not set
Contact customer service
Battery on MSB is
discharged or defective
Contact customer service
Real-time clock
defective
Contact customer service
W111 Many EEPROM write cycles
within the last 6 minutes
A very large number of
write commands were
issued through
interfaces. Over time,
this reduces the service
life of the EEPROM.
Remove the excess write accesses from
your control program
E112 Impermissible DIP switch
setting
The DIP switch on the
MSB has an invalid
position
Contact customer service
MSB defective Contact customer service
W113 The device ID does not
match the recognized
backing pump
The DIP switch on the
MSB has an invalid
position
Contact customer service
Type of backing pump
was not or was
incorrectly detected
Contact customer service
MSB defective Contact customer service
W122 No response from bus
module
Connection to BUS
module interrupted
Check the connection to the bus module
Replace the connection cable to the bus
module
Bus module defective Replace the bus module
Bus module connection
on the device defective
Contact customer service