overload alarm function.
Setting range: 0x000–0x131
LED ones:
0: Motor overload alarm, relative to the rated
current of the motor
1: Inverter overload alarm, relative to the rated
current of the inverter
LED tens:
0: The inverter continues working after
overload/underload alarm.
1: The inverter continues working after
underload alarm reporting but it stops
running upon an overload fault.
2: The inverter continues working after overload
alarm reporting but it stops running upon an
underload fault.
3: The inverter stops running after
overload/underload alarm reporting.
LED hundreds:
0: Detection all the time
1: Detection in constant running
Setting range of P11.09: 100%–200%
Setting range of P11.10: 0.1–3600.0s
This parameter is used to set the speed
deviation detection time.
Note: Speed deviation protection is disabled
when P11.14 is set to 0.0.