Goodrive30 Series VFD Product overview
-5-
2 Product overview
2.1 Quick startup
2.1.1 Unpacking inspection
Check as follows after receiving products:
1. Check whether the packing box is damaged or dampened. If yes, contact local dealers
or INVT offices.
2. Check the model identifier on the exterior surface of the packing box is consistent with
the purchased model. If no, contact local dealers or INVT offices.
3. Check whether the interior surface of packing box is abnormal, for example, in wet
condition, or whether the enclosure of the VFD is damaged or cracked. If yes, contact
local dealers or INVT offices.
4. Check whether the name plate of the VFD is consistent with the model identifier on the
exterior surface of the packing box. If no, contact local dealers or INVT offices.
5. Check whether the accessories (including user's manual and control keypad) inside the
packing box are complete. If not, please contact with local dealers or INVT offices.
2.1.2 Checking before applying
Check the machine before beginning to use the VFD:
1. Check the load type to verify that there is no overload of the VFD during work and
check whether the power class of the VFD needs to be increased.
2. Check whether the actual running current of the motor is less than the rated current of
the VFD.
3. Check whether the control accuracy required by the load is the same with that of the
VFD.
4. Check whether the grid voltage is consistent with the rated voltage of the VFD.
2.1.3 Environment confirmation
Check as follows before the actual installation and usage:
1. Check whether the ambient temperature of the VFD exceeds 40°C. If it exceeds 40°C,
derate 1% for every increase of 1°C. It is not recommended to use the VFD if the
ambient temperature exceeds 50°C.
Note: For the cabinet VFD, the ambient temperature means the air temperature inside
the cabinet.
2. Check whether the ambient temperature of the VFD in actual use is lower than -10°C. If
yes, use heating facilities.
Note: For the cabinet VFD, the ambient temperature means the air temperature inside
the cabinet.
3. Check whether the altitude of the VFD in actual use exceeds 1000m. If it exceeds
1000m, derate 1% for every increase of 100m. When the altitude exceeds 3000m,