Goodrive30 Series VFD Communication protocol
-131-
RTU master command (sent from the
master to the VFD)
RTU slave response (sent from the VFD to
the master)
START
T1-T2-T3-T4
START
T1-T2-T3-T4
ADDR
02H
ADDR
02H
CMD
06H
CMD
06H
High-order bit of data
writing address
00H
High-order bit of data
writing address
00H
Low-order bit of data
writing address
04H
Low-order bit of data
writing address
04H
Data content
high-order bit
13H
Data content
high-order bit
13H
Data content
low-order bit
88H
Data content
low-order bit
88H
CRC CHK low-order
bit
C5H
CRC CHK low-order
bit
C5H
CRC CHK high-order
bit
6EH
CRC CHK high-order
bit
6EH
END
T1-T2-T3-T4
END
T1-T2-T3-T4
Note: Sections 7.2 and 7.3 mainly describe the command formats.
7.3.3 Command code 08H, diagnosis
Sub-function code description:
Sub-function code
Description
0000
Return data based on query requests
For example, to query about the circuit detection information about the VFD whose address is
01H, the query and return strings are the same, and the formats are described in the following
tables.
RTU master command
RTU slave response
START
T1-T2-T3-T4
START
T1-T2-T3-T4
ADDR
01H
ADDR
01H
CMD
08H
CMD
08H
Sub-function code
high-order bit
00H
Sub-function
code high-order
bit
00H
Sub-function code
low-order bit
00H
Sub-function
code low-order bit
00H
Data content
high-order bit
12H
Data content
high-order bit
12H

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals