Goodrive30 Series VFD Function parameter list
-40-
Restoring the default values may delete the
user password. Exercise caution when using
this function.
P01 group Start and stop control
0: Direct start: start from the starting frequency
P01.01.
1: Start after DC braking: start the motor from the
starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Speed tracking restart: The direction and
speed will be tracked automatically for the
smoothing starting of rotating motors. It is
suitable in the cases where reverse rotation may
occur to the high inertia load during starting.
Note: The function is available only for 4kW and
higher models.
Starting
frequency
of direct
start
The function code indicates the initial frequency
during VFD start. See P01.02 (Starting
frequency hold time) for detailed information.
Setting range: 0.00–50.00Hz
Starting
frequency
hold time
Output frequency
fmax
t1
T
f1 set by P01.01
f1
t1 set by P01.02
Setting a proper starting frequency can increase
the torque during VFD start. During the hold time
of the starting frequency, the output frequency of
the VFD is the starting frequency. And then, the
VFD runs from the starting frequency to the set
frequency. If the set frequency is lower than the