Goodrive30 Series VFD Function parameter list
-39-
and electrical magnetic interference will
increase.
On the contrary, an extremely-low a carrier
frequency may cause unstable operation at low
frequency, decrease the torque, or even lead to
oscillation.
The carrier frequency has been properly set in
the factory before the VFD is delivered. In
general, you do not need to modify it.
When the frequency used exceeds the default
carrier frequency, the VFD needs to derate by
10% for each increase of 1k carrier frequency.
Setting range: 1.0–15.0kHz
Motor
parameter
autotuning
0: No operation
1: Rotary autotuning. Comprehensive motor
parameter autotuning. It is recommended to use
rotating autotuning when high control accuracy is
needed.
2: Static autotuning 1 (comprehensive
autotuning); static autotuning 1 is used in cases
where the motor cannot be disconnected from
load.
3: Static autotuning 2 (partial autotuning); when
the present motor is motor 1, only P02.06,
P02.07 and P02.08 are autotuned.
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the VFD can
eliminate the impact on the output voltage of the
VFD because of the bus voltage fluctuation.
Function
parameter
restore
0: No operation
1: Restore default values
2: Clear fault records
Note:
After the selected operation is performed,
the function code is automatically restored to
0.