Goodrive30 Series VFD Function parameter list
-103-
Function
code
Name
Description
Default
Modify
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
Setting range of P11.15: 0.010.0s
P11.16
Automatic
frequency
reduction
during
voltage
drop
0: Disable
1: Enable. When the grid voltage drops to the
rated voltage, the VFD ensures the rated output
torque by automatic frequency reduction.
0
P13 group SM control
Function
code
Name
Description
Default
Modify
P13.00
Pull-in
current
reduction
coefficient
0.0100.0%
80.0%
P13.01
Initial pole
detection
method
0: Do not detect
1: High-frequency superposition (reserved)
2: Pulse superposition
0
P13.02
Pull-in
current 1
Pull-in current is the pole positioning current.
Pull-in current 1 is valid within the lower limit of
pull-in current switchover frequency threshold. If
you need to increase the starting torque,
increase the value of the function code properly.
Setting range: 0.0%100.0% (of the motor rated
current)
20.0%
P13.03
Pull-in
current 2
Pull-in current is the pole positioning current.
Pull-in current 2 is valid within the upper limit of
pull-in current switchover frequency threshold.
Generally, you do not need to modify the function
10.0%

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals