Goodrive30 Series VFD Function parameter list
-103-
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running Fault output
Setting range of P11.15: 0.0–10.0s
Automatic
frequency
reduction
during
voltage
drop
0: Disable
1: Enable. When the grid voltage drops to the
rated voltage, the VFD ensures the rated output
torque by automatic frequency reduction.
P13 group SM control
Pull-in
current
reduction
coefficient
Initial pole
detection
method
0: Do not detect
1: High-frequency superposition (reserved)
2: Pulse superposition
Pull-in current is the pole positioning current.
Pull-in current 1 is valid within the lower limit of
pull-in current switchover frequency threshold. If
you need to increase the starting torque,
increase the value of the function code properly.
Setting range: 0.0%–100.0% (of the motor rated
current)
Pull-in current is the pole positioning current.
Pull-in current 2 is valid within the upper limit of
pull-in current switchover frequency threshold.
Generally, you do not need to modify the function