Goodrive30 Series VFD Function parameter list
-99-
P11 group Protection parameters
Function
code
Name
Description
Default
Modify
P11.00
Phase loss
protection
0x000x11
Ones place:
0: Disable input phase loss protection
1: Enable input phase loss protection
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
11
P11.01
Frequency
drop at
transient
power-off
0: Enable
1: Disable
0
P11.02
Frequency
drop ratio at
transient
power-off
Setting range: 0.00Hz/sP00.03 (max. output
frequency)
After the grid powers off, the bus voltage drops
to the frequency drop point at transient
power-off, the VFD begins to decrease the
running frequency based on P11.02, to make the
motor generate power again. The returning
power can maintain the bus voltage to ensure a
rated running of the VFD until the VFD is
powered on again.
Voltage degree
220V
380V
660V
Frequency drop
point at transient
power-off
260V
460V
800V
Note:
Adjust the parameter properly to avoid the
stopping caused by VFD protection during
the switching of the grid.
Disable the input phase loss protection
before enabling this function.
10.00Hz/s
P11.03
Overvoltage
stall
protection
0: Disable
1: Enable
1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals