Goodrive30 Series VFD Function parameter list
-100-
Function
code
Name
Description
Default
Modify
Overvoltage
stall threshold
Output
frequency
Time t
Time t
DC bus voltage V
P11.04
Overvoltage
stall
protection
voltage
110150% (standard bus voltage) (380V)
130%
110150% (standard bus voltage) (220V)
120%
P11.05
Current limit
action
During accelerated running, as the load is too
large, the actual acceleration rate of motor is
lower than that of output frequency, if no
measures are taken, the VFD may trip due to
overcurrent during acceleration.
Ones place: Current limit action selection
0: Invalid
1: Always valid
Tens place: Hardware current limit overload
alarm selection
0: Valid
1: Invalid
01
P11.06
Automatic
current limit
level
Current limit protection function detects output
current during running, and compares it with the
current-limit level defined by P11.06, if it exceeds
the current-limit level, the VFD will run at stable
frequency during accelerated running, or run in
decreased frequency during constant-speed
running; if it exceeds the current-limit level
continuously, the VFD output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower
than the current-limit level again, it will continue
accelerated running.
160.0%
P11.07
Frequency
drop rate
during
current limit
10.00Hz/s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals