Goodrive30 Series VFD Function parameter list
-73-
AO1 output
correspondi
ng to lower
limit
range, the output uses the lower limit or upper
limit.
When the analog output is current output, 1mA
equals 0.5V.
In different cases, the corresponding analog
output of 100% of the output value is different.
See each application for detailed information.
Setting range of P06.17: -100.0%–P06.19
Setting range of P06.18: 0.00–10.00V
Setting range of P06.19: P06.17–100.0%
Setting range of P06.20: 0.00V–10.00V
Setting range of P06.21: 0.000–10.000s
Setting range of P06.22: -100.0%–P06.24
Setting range of P06.23: 0.00–10.00V
Setting range of P06.24: P06.22–100.0%
Setting range of P06.25: 0.00–10.00V
Setting range of P06.26: 0.000–10.000s
Upper limit
of AO1
output
AO1 output
correspondi
ng to upper
limit
Lower limit
of AO2
output
AO2 output
corrspondin
g to lower
limit
Upper limit
of AO2
output
AO2 output
correspondi
ng to upper
limit
P07 group HMI
0–65535
When you set the function code to a non-zero
number, password protection is enabled.
If you set the function code to 00000, the
previous user password is cleared and password