Goodrive30 Series VFD Function parameter list
-38-
Function
code
Name
Description
Default
Modify
Modify P00.13 to shift the rotation direction of the
motor. This effect equals to the shifting the
rotation direction by adjusting either two of the
motor lines (U, V and W). The motor rotation
direction can be changed by QUICK/JOG on the
keypad. Refer to parameter P07.02 for details.
Note: When the function parameter comes back
to the default value, the motor’s running direction
will come back to the factory default state. In
some cases it should be used with caution after
commissioning if the change of rotation direction
is disabled.
2: Forbid to run in reverse direction, it can be
used in some special cases if the reverse
running is disabled.
P00.14
Carrier
frequency
Carrier
frequency
Electro magnetic
noise
Noise and leakage
current
Heating
eliminating
High
LowHigh
Low
High
Low
The relationship between models and carrier
frequencies is as follows:
Model
Default carrier
frequency
0.411kW
8kHz
1555kW
4kHz
75110kW
2kHz
Advantage of high carrier frequency: ideal
current waveform, little current harmonic wave
and motor noise.
Disadvantage of high carrier frequency:
increasing the switch loss, increasing VFD
temperature and the impact to the output
capacity. The VFD needs to derate on high
carrier frequency. At the same time, the leakage
Model
depended

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive30 VFD Series and is the answer not in the manual?

INVT Goodrive30 VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive30 VFD Series
CategoryInverter
LanguageEnglish

Related product manuals