Modify P00.13 to shift the rotation direction of the
motor. This effect equals to the shifting the
rotation direction by adjusting either two of the
motor lines (U, V and W). The motor rotation
direction can be changed by QUICK/JOG on the
keypad. Refer to parameter P07.02 for details.
Note: When the function parameter comes back
to the default value, the motor’s running direction
will come back to the factory default state. In
some cases it should be used with caution after
commissioning if the change of rotation direction
is disabled.
2: Forbid to run in reverse direction, it can be
used in some special cases if the reverse
running is disabled.
Advantage of high carrier frequency: ideal
current waveform, little current harmonic wave
and motor noise.
Disadvantage of high carrier frequency:
increasing the switch loss, increasing VFD
temperature and the impact to the output
capacity. The VFD needs to derate on high
carrier frequency. At the same time, the leakage