Sin: Three-wire control; FWD: Forward running;
REV: Reverse running
Note: For 2-wire controlled running mode, when
the FWD/REV terminal is valid, if the VFD stops
due to a stop command given by another source,
the VFD does not run again after the stop
command disappears even if the control terminal
FWD/REV is still valid. To make the VFD run,
you need to trigger FWD/REV again, for
example, PLC single-cycle stop, fixed-length
stop, and valid STOP/RST stop during terminal
control. (See P07.04).
The function codes specify the delay time
corresponding to the electrical level changes
when the programmable input terminals switch
on or switch off.