Chapter 6
Controller V6 Touch
ITW Dynatec
DM55 DynaDrum PP V6, Manual No.21-18, Rev.2.19 Page 51
Item Description
1
Status Line
Display of the actual status of the unit:
READY = All zones are within their set point temperatures and the unit is ready for
operation.
RUNNING = All zones are within their set point temperatures and the unit/pump is running.
NOT READY = At least one zone has not yet reached its set point temperature or has fallen
below its set point or it is lower than the set global release temperature.
STANDBY = Standby temperature is activated.
ALARM = Alarms or faults are active.
The status line is highlighted green when the system is READY or RUNNING, yellow when
NOT READY, grey when in STANDBY and red when in ALARM condition.
The status line along with “Systems” button is in orange color if a non-visible system goes into
Alarm condition (if f several systems are controlled by the HMI).
The „clock“ icon appears if a timer is activated under „Time & Scheduler“ screen and
disappears if the timer is deactivated.
Display of the actual date and time are on the right side of the screen.
Depending on the selection of the unit of temperature and pressure (°C and bar or °F and psi)
made under Unit & Date Selection, the appearance of the date display is affected also. With
the C/bar selection, the date is displayed as ‘day.month.year’ while in F/psi mode, the date is
displayed as ‘month/day/year’.
The time is displayed as hour.minutes.seconds (ie, 11:48:25 pm).
By pressing the status line you go to the Log Book screen.
2
Icon Line
ACT / SET: Indicates if the temperature values shown on the display are Actual or Set point
values. The Actual values will be displayed during production. By pressing the
Set/Act button, the Set values can be displayed and edited. The display returns
automatically to the Actual values after about 15 seconds if there is no activity.
The icons:
Platen
Filter block
Hose
Applicator
Auxiliary components
Pump RPM
Pressures
Decentralized pumps (e.g. Applicator, Metering Station: A plausible limit value of
Input Pressure (a minimum pressure of not less than 2 bar is recommended) has to be
entered to avoid a dry run of the pumps; otherwise the pump can be damaged. See
point “Extended Pump Mode Settings Screen, Linear Line Speed, Pressure Control”.
The appropriate actual values (temperature, pump rpm, pressures) are displayed under the
icons.