FX-1/FX-1R Maintenance Manual
13-10-2. Replacing the UPS Battery
WARNING
To prevent fatal accidents due to electrical shock, always turn OFF
the main switch firmly.
Make sure that the main circuit breaker and the main switch of the
machine main unit are turned OFF. The main switch described
above is the power switch installed in the building and is not the
power switch of the machine main unit.
13-10-2-1. Detaching the UPS
(1) Disconnect the connectors connected to the UPS and the relay connectors of the cable coming
from the UPS.
Disconnect the
connector from the
communication
connector.
Remove the screw
of the metallic
plate for securing
the UPS.
Disconnect the
plug from the
output socket.
(2) Remove the screw of the metallic plate for securing the UPS main unit, and then pull out the
UPS toward the front.
13-42
Rev. 2.00