WARNING: The AC power cord for the switch is intended for use with the switch only
and not for any other use.
WARNING:
Translaon from Japanese: The aached power cable is only for this product. Do not
use the cable for another product.
NOTE: In North America, AC power cords must not exceed 4.5 m (approximately 14.75 ) in
length, to comply with Naonal Electrical Code (NEC) Secons 400-8 (NFPA 75, 5-2.2) and
210-52, and Canadian Electrical Code (CEC) Secon 4-010(3). You can order AC power cords
that are in compliance.
WARNING: The switch is pluggable type A equipment installed in a restricted-access
locaon. It has a separate protecve earthing terminal (sized for UNC 1/4-20 ground
lugs) provided on the chassis in addion to the grounding pin of the power supply cord.
This separate protecve earthing terminal must be permanently connected to earth.
CAUTION: Power cords must not block access to switch components. We recommend
that you route all AC power cord cables through the power cord tray provided with the
switch.
AC Power Supply Specicaons for EX9214 Switches
Table 14 on page 49 lists the power supply specicaons for an AC power supply used in EX9214
switches.
48