Four power supplies provide full redundancy. If a power supply in a redundant conguraon is removed
or fails, its redundant power supply takes over without interrupon. The power supply in PEM2 serves
as redundant power supply to the power supply in slot PEM0 and the power supply in PEM3 serves as
redundant power supply to the power supply in slot PEM1.
SEE ALSO
Connecng DC Power to an EX9214 Switch | 179
DC Power Supply Specicaons for EX9214 Switches
Table 17 on page 54 lists the DC power supply specicaons for EX9214 switches.
Table 17: DC Power Supply Specicaons for an EX9214 Switch
Item Specicaons
Maximum output power
• 4100 W in two-feed mode
• 1700 W in one-feed mode
DC input voltage
• Nominal operang range: –48 VDC
• Operang voltage range: –40 VDC to –72 VDC
DC nominal input current rang @ 48
VDC
• 104 A for both feeds (54 A and 50 A per feed) in two-feed mode
• 42 A in one-feed mode
Maximum input current rang @ 40 VDC
input voltage
• 128 A for both feeds (66 A and 62 A per feed) in two-feed mode
• 52 A in one-feed mode
Table 18 on page 55 lists the power system specicaons for EX9214 switches.
54