EasyManua.ls Logo

Kidde Fire Systems ARIES NETLink

Kidde Fire Systems ARIES NETLink
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Networking
February 2012 5-8 P/N 06-237058-001
5-8.2.3 PROCESS GROUP 0 EVENTS
Each control unit can be configured to Process Group 0 Events. This means that a node
will process events from a group 0 node in addition to commands. A node configured
with a non-zero group number and to Process Group 0 Events would be capable of the
following interactions:
Displaying and logging all network events from nodes within its group or group 0
Activating its outputs upon any initiating event from all control in its group or
group 0
Issuing acknowledge, silence, and reset commands to all control units in its group
or group 0
Processing acknowledge, silence, and reset commands from all control units in
its group or group 0
Figure 5-5 shows the possible interactions among the various members of a selectively
signaling networked system with groupings, with one control unit designated as the
master control unit and with group nodes also configured to process group 0 events.

Table of Contents

Related product manuals