Troubleshooting
P/N 06-237058-001 7-7 February 2012
EVENT MEMORY WRITE
FAILURE On
Faulty storage Use the PC configuration software to
download the event log and forward an
electronic copy to Kidde Technical
Services. Refer to the configuration
software user's guide.
Re-initialize the control unit by first
removing, and then re-applying, primary
and secondary power sources
Functionally test the system
DATE/TIME MUST BE SET
TROUBLE On
Message appears if the Real Time Clock
chip on the Main Controller Board has a
problem.
• Set the date and time as instructed in
Section 4-9.2.
• Check the lithium cell battery on the Main
Controller Board and replace if necessary.
Table 7-2. SLC Events
SLC Events
For the following SLC-related events, L# is the SLC loop number and Addr is the
device address.
Error Message Probable Cause Corrective Action
L#: Addr
SWITCH NOT SET On
AlarmLine Module
An incorrect configuration for the AAM
at address L#: Addr, where L# is the
SLC loop number and Addr is the
device address.
Check the configuration settings for
the AAM. Re-configure and upload
the correct configuration.
Refer to AlarmLine Installation,
Operation, and Maintenance Manual,
P/N 73.04
L#: Addr
24 VDC FAILURE On
Signal/ Sounder
Failure of the DC-to-DC converter in the
ASM at address L#: Addr
Refer to ASM Installation
Instructions, P/N 06-235717-001.
Check 24 Vdc power connections to
ASM.
Ensure that the ASM's Jumper P1
and Switch S1 are set for 24 Vdc
operation
Replace the ASM if steps above are
unsuccessful
Table 7-1. General System Events (Continued)
General System Events
Error Message Probable Cause Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ARIES NETLink and is the answer not in the manual?

Kidde Fire Systems ARIES NETLink Specifications

General IconGeneral
BrandKidde Fire Systems
ModelARIES NETLink
CategoryControl Unit
LanguageEnglish

Related product manuals