Troubleshooting
P/N 06-237058-001 7-15 February 2012
L#: Addr
HIGH AIRFLOW On
ORION XT Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by a
PALM/APIC. Excessively high air flow
through the piping system
• Look for leaks in the HSSD's piping
system
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD. The airflow
may need to re- normalized.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
L#: Addr
LOW AIRFLOW On
ORION XT Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by a
PALM/APIC. Low air flow through the
piping system
• Look for blockages in the HSSD's
piping system
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD. The airflow
may need to re-normalized.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
L#: Addr
OFFSET TROUBLE On
ORION XT Interface Module
The PALM/APIC at address L#: Addr is
reporting an offset problem with the
HSSD that it is monitoring. This is
probably a problem with the
background obscuration level in the
area of the HSSD.
• Work with the end user to improve the
air quality in the HSSD location.
• Check the PALM/APIC-to-HSSD
connections
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
Table 7-2. SLC Events (Continued)
SLC Events
For the following SLC-related events, L# is the SLC loop number and Addr is the
device address.
Error Message Probable Cause Corrective Action