Troubleshooting
P/N 06-237058-001 7-15 February 2012
L#: Addr
HIGH AIRFLOW On
ORION XT Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by a
PALM/APIC. Excessively high air flow
through the piping system
• Look for leaks in the HSSD's piping
system
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD. The airflow
may need to re- normalized.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
L#: Addr
LOW AIRFLOW On
ORION XT Interface Module
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by a
PALM/APIC. Low air flow through the
piping system
• Look for blockages in the HSSD's
piping system
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD. The airflow
may need to re-normalized.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
L#: Addr
OFFSET TROUBLE On
ORION XT Interface Module
The PALM/APIC at address L#: Addr is
reporting an offset problem with the
HSSD that it is monitoring. This is
probably a problem with the
background obscuration level in the
area of the HSSD.
• Work with the end user to improve the
air quality in the HSSD location.
• Check the PALM/APIC-to-HSSD
connections
• Use ORION Configuration Software or
AIR-Intelligence Remote
Configuration Software to
troubleshoot the HSSD.
• Refer to ORION XT Installation,
Operation, and Maintenance Manual,
P/N 06-236005-401 or appropriate
AI R- In t e l li ge nc e d e te c t or ma n u a l,
P/N 33-308100-001/-002/-003.
Table 7-2. SLC Events (Continued)
SLC Events
For the following SLC-related events, L# is the SLC loop number and Addr is the
device address.
Error Message Probable Cause Corrective Action

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde Fire Systems ARIES NETLink and is the answer not in the manual?

Kidde Fire Systems ARIES NETLink Specifications

General IconGeneral
Remote AccessYes
Power Supply24 VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
DimensionsVaries by model
WeightVaries by model

Related product manuals