Troubleshooting
February 2012 7-24 P/N 06-237058-001
LAM
Addr
RAM FAILURE On • Re-initialize the control unit by first
removing, and then re-applying,
primary and secondary power
sources
• Functionally test the system
LAM
Addr
CONFIGURATION FAULT On • Re-initialize the control unit by first
removing, and then re-applying,
primary and secondary power
sources
• Reconfigure the module using PC
configuration software or the control
unit menu
• Functionally test the system.
LAM
Addr
PROGRAM MEMORY FAULT On • Re-initialize the control unit by first
removing, and then re-applying,
primary and secondary power
sources
• Functionally test the system
Table 7-6. Remote-Display/Annunciator Events
Remote-Display/Annunciator Events
Error Message Probable Cause Corrective Action