August 2013 3-46 P/N 06-236530-001
3-2.5.2.4.15 How to Manually De-Register SLC Devices
Purpose: To remove one or more SLC devices from the ARIES Control
Unit’s configuration memory. The de-registered device(s) must be
physically removed from the SLC prior to or following the execution of
the De-Registration Procedure.
3-2.5.2.4.16 How to Disable the Flashing LEDs on SmartOne Detectors
Purpose: To prevent one or more SmartOne detector LEDs from
flashing in standby operation. LEDs will only illuminate in alarm
condition. The detectors' default-LED operation is flashing.
CAUTION
Remove all references to the de-registered devices from the system's
application (i.e., EOC) program.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press 3 Key Access "SLC Devices" option
5 Press "Scroll" Key Access additional options
6 Press 4 Key Select "De-Registration"
7 Use keypad to select address or range of
addresses to de-register.
Press "Enter" Key to confirm selection.
Specify addresses to de-register
8 Wait until "Device DeRegistration" message
disappears from the display.
Devices de-register or fail.
9 Exit Menu System
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 3 Key Enter Set-Menu branch
4 Press 3 Key Access "SLC Devices" option
5 Press "Scroll" Key Access additional options
6 Press 5 Key Select "Blink Control"
7 Use keypad to select address or range of
addresses to disable LED flashing.
Press "Enter" Key to confirm selection.
Specify addresses to disable flashing LEDs in
normal operation
8 Press 1 Key and then press "Enter" Key to confirm
selection.
Disable flashing LEDs
9 Wait until the message appears in the display,
completed or failed.
Number of detectors are shown.
10 Exit Menu System