P/N 06-236530-001 3-81 August 2013
3-2.5.2.5.2 How to Run an Audible Walk Test
Purpose: To suspend normal system operation for functional testing of
one or more SmartOne initiating devices.
The ARIES Control Unit will not display and act upon alarm reports from
initiating devices selected for walk testing. There is no need for the
operator to acknowledge, silence, or reset an event initiated during a
walk test. The control unit will only energize outputs programmed for
walk-test activation for a period of one second following the receipt of
an alarm signal from any of the devices selected for walk testing.
Outputs programmable for walk testing include control unit-based
NACs and combination circuits configured as NACs and SLC-based
output modules (such as ASMs and AOs).
The most-current walk-test results for all initiating devices are stored
in the walk-test log. The walk-test mode will automatically end after 30
minutes of inactivity. It can also be ended by a system reset or by the
procedure in Paragraph 3-2.5.2.5.4.
Any initiating devices not selected for walk testing will report events as
normal. Any alarm reported during a walk test will end the walk-test
mode and cause the alarm report to be processed as described in
Paragraph 3-2.5.4.
Step Action Result
1 Press 0 Key Initiate menu access
2 Enter Password; Press “Enter” Key Gain access to menus
3 Press 4 Key Enter Test-Menu branch
4 Press "Scroll" Key Access additional options
5 Press 5 Key Select "Alarm Sim Test"
6 Press 1 Key to select SLC Alarm Simulation or
Press 2 Key to select HSD Alarm Simulation
Specify device type to be alarm simulated
7 Enter the SLC or HSD Address of the device to
test. Use XXX format for address.
Press "Enter" Key to confirm address selection.
Specify the address of the device being tested
8 Press 1 Key and Press “Enter” Key Initiate simulation
9 Press "Acknowledge" and "Silence" Keys (as
appropriate)
Execute proper operator procedures
10 Repeat Steps 7 to 9 (as required) Simulate multiple-device actuations
11 De-activate all simulated initiating devices See Paragraph 3-2.5.2.5.9
12 Press "Backspace" Key (as required) Exit Menu System
13 Press “Reset” Switch Resume Normal Operations
CAUTION
Physically disconnect the wiring to all agent-release and pre-action-sprinkler
circuits before walk testing any SLC initiating devices. Restore the system to
normal operating condition at the conclusion of these tests and any other
functional tests that were performed.