Chapter 3: System operation
P/N 3102352-EN • REV 005 • ISS 28DEC18 157
To start a walk test:
1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Enter a level one password.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID for the zone to be tested.
6. Choose Start.
7. Conduct the walk test.
8. Press Cancel to return to the previous menu.
or
Press the Menu button to exit menu mode.
Note: To see the activation and restoration of all walk test events, the panel must be reset
prior to ending the walk test. Once the reset is complete, you can end the walk test and view a
walk test report.
To end a walk test:
1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Choose either All Devices or Zone.
4. If you chose Zone, enter the zone ID of the zone where you are ending the walk test.
5. Choose End to turn off the walk test. All of the devices that were activated in the test are
restored at this time.
6. Press Cancel to return to the previous menu.
or
Press the Menu button to exit menu mode.

Table of Contents