EasyManua.ls Logo

Kidde FX-64

Kidde FX-64
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B: Worksheets
198 P/N 3102352-EN • REV 005 • ISS 28DEC18
Figure 56: Device circuit path diagram
FACP
J
J
10 ft
(3 m)
200 ft
(61 m)
30 ft
(9 m)
J
100 ft
(30 m)
1000 ft
(305 m)
200 ft
(61 m)
100 ft
(30 m)
Table 52: Twisted shielded and nontwisted shielded (evenly distributed shielded)
Number of
detectors
Number of
modules (1
or 2
channel)
Maximum allowable wire distance using Twisted shielded and nontwisted
shielded wire pairs (evenly distributed shielded)
18 AWG
16 AWG
14 AWG
ft.
m
ft.
m
ft.
m
1 to 25
0 to 75
5172
1577
6098
1859
5952
1815
26 to 50
0 to 75
5172
1577
6098
1859
5952
1815
51 to 75
0 to 75
5172
1577
6098
1859
5952
1815
76 to 100
0 to 75
5172
1577
6098
1859
5952
1815
101 to 125
0 to 75
5172
1577
6098
1859
5952
1815
0
76 to 100
5172
1577
6098
1859
5952
1815
1 to 25
76 to 100
5172
1577
6098
1859
5952
1815
26 to 50
76 to 100
5172
1577
6098
1859
5952
1815
51 to 75
76 to 100
5172
1577
6098
1859
5952
1815
76 to 100
76 to 100
5172
1577
6098
1859
5952
1815
101 to 125
76 to 100
5172
1577
6098
1859
5952
1815
0
101 to 125
5172
1577
6098
1859
5952
1815
1 to 25
101 to 125
5172
1577
6098
1859
5952
1815
26 to 50
101 to 125
5172
1577
6098
1859
5952
1815
51 to 75
101 to 125
5172
1577
6098
1859
5952
1815
76 to 100
101 to 125
5172
1577
6098
1859
5952
1815
101 to 125
101 to 125
5172
1577
6098
1859
5952
1815