Chapter 2: Front panel programming
50 P/N 3102352-EN • REV 005 • ISS 28DEC18
Description
Photoelectric smoke and CO detectors (PCD)
For smoke + CO detectors that trigger an active alarm event (smoke or CO).
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO monitor
latching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO monitor
nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching monitor event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for monitor nonlatching.
Smoke alarm + CO
supervisory latching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
latching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored and the control panel is reset.
Smoke alarm + CO
supervisory nonlatching
For smoke + CO detectors that trigger an active alarm event (smoke) or a CO
nonlatching supervisory event.
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.
rvisory latching +
For smoke + CO detectors that trigger a supervisory latching event (smoke) or an
active alarm event (CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory latching
For smoke + CO detectors that trigger a supervisory latching event (smoke or
CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.
Smoke supervisory latching +
CO supervisory nonlatching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or a
supervisory nonlatching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored. Resetting the control panel is required to restore the smoke
type event. Resetting the control panel is not required for supervisory
nonlatching.
Smoke supervisory latching +
CO monitor latching
For smoke + CO detectors that trigger a supervisory latching event (smoke) or
monitor latching event (CO).
Detectors with this device type remain active until the condition that activated
them is restored and the panel is reset.