Chapter 2: Front panel programming
P/N 3102352-EN • REV 005 • ISS 28DEC18 55
Table 16: Monitor device types
Device type
Description
Monitor
Monitoring of normally open switches for other functions (fire door position, etc.).
Not approved for use under CAN/ULC-S527 in Canada.
Table 17: Output device types
Device type
Description
Continuous nonsilenceable
For nonsilenceable strobes and notification appliances that generate a temporal
pattern. [2]
Continuous nonsilenceable
(latched)
For latching strobes and notification appliances that generate a temporal pattern.
Continuous silenceable
For strobes and notification appliances that generate a noncoded tone.
Genesis audible
visible
silence
For Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced
Integrity appliances maintain synchronization per UL 1971. For Genesis devices
only, connected horns can be silenced and strobes turn off.
Genesis nonsilenceable
For Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced
Integrity appliances maintain synchronization per UL 1971. For Genesis devices
only, connected horns cannot be silenced and strobes on the same two-wire circuit
flash until the panel is reset. [2]
Relay nonsilenceable
For relay devices that do not follow signal silence [2]
Relay nonsilenceable
(latched)
For relay devices that do not follow signal silence and do not restore until manually
unlatched
Relay silence
For relays that turn off when you press Signal Silence. [2]
Supervised output
For modules that output an unsynchronized signal and that do not turn off when
you press Signal Silence.
Supervised output (latched)
For latched output modules that output an unsynchronized signal and that do not
turn off when you press Signal Silence.
Auto sync output
Silenceable
For generating sound patterns on sounder bases for carbon monoxide (CO) and
fire signals. Signals turn off when you press Signal Silence. Only patterns from
T3T4 are silenced.
Auto sync output
nonsilenceable
For generating sound patterns on sounder bases for carbon monoxide (CO) and
fire signals.
Unlatch outputs
For output modules that are configured to manually unlatch latched outputs [1]
[1]
The following input modules can be configured to unlatch latched outputs: FX-IDC1A, FX-IDC1B, FX-IDC2B,
or RZI16-2RS.
[2] Supports Standalone mode of operation.
Table 18: NAC modules
Device type
Description
Genesis
-audible/visible silence For Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced
Integrity appliances maintain synchronization per UL 1971. For Genesis devices
only, connected horns can be silenced and strobes turn off. [1]