Chapter 2: Front panel programming
62 P/N 3102352-EN • REV 005 • ISS 28DEC18
6. Choose a function to assign to the key.
None
Activate
Unlatch
Restore
Note: To disable a programmed key, choose None.
7. If you chose Unlatch in step 6:
• Press Enter to reopen the previous menu, and then choose Save.
— or —
Press the Menu button to exit menu mode without saving.
The button is now completely programmed to unlatch all latched outputs globally.
8. If you chose Disable, press the down arrow to edit the Control option, and indicate what the
key should control. Choose:
• Members
• Corr Grp
• Both
Press Enter to reopen the previous menu, and then choose Save.
Note: This option is not available for Unlatch, Activate, or Restore.
You are now ready to choose the correlation groups to be activated, disabled, or restored.
9. Enter the number of the first correlation group to be assigned or unassigned, and then
press Enter.
• If you enter the number of a correlation group that is already assigned to the key, the
command REM (remove) is displayed. Pressing Enter removes the group from the list.
• If you enter the number of a correlation group that has not yet been assigned to the key,
the command ADD is displayed. Pressing Enter adds the new group to the list.
10. Enter the number of the next correlation group to be added or removed, and then press
Enter. Repeat to add or remove any remaining correlation groups.
11. When you have finished editing the list of correlation groups, press Enter to reopen the
previous menu, and then choose Save.
— or —
Press the Menu button to cancel your changes and exit menu mode.
12. Press the Menu button to exit menu mode. The button is now programmed to activate,
disable, or restore all correlation groups that you have added to the list.