56
01/13424999386
6 Cable lengths diagram
Cable lengths diagram for determining the required cable cross-sections in relation to the cable length and the
sum of the drive rated currents.
6.1 Formulaforcalculatingthecablecross-section
ρ x 2 x L x I
A =
U
A = Cable cross-section, A / mm²
ρ=Specicresistanceofelectriccables,ρ=0.0175(Ω*mm²)/m
2 x L = 2 x line length, L /m (outward and return line)
I = Sum of the rated currents of the connected drives, I / A
U = Max. voltage drop, U = 2.5 V
Note: Observe permitted current outputs, see Technical data.
2 x line length included in cable lengths diagram.
Easy-
Connect+
Cable length L / m
Cable cross-section A
2 x L / m
EasyConnect+
0
50
100
150
200
250
300
350
400
450
12345678910111213141516
0
1

m (einfache Leitungslänge)
Nennstrom Antrieb in Ampere
a)
b)
c)
d)
e)
50
100
150
200
250
300
350
400
450
500
2
3
4
5
6
78

a)
b)
c)
d)
e)
0
20
40
60
80
100
120
140
160
2,5
3
3,5
5
6
7
8
4
4,5
5,5
6,5
7,5
a) 1,5 mm²
b) 2,5 mm²
c) 4 mm²
d) 2 x 2,5 mm²
e) 6 mm²
m (einfache Leitungslänge)
Nennstrom Antrieb in Ampere


0
50
100
150
200
250
300
350
400
123456789101112
A [mm²] = 1,5
A [mm²] = 2,5
A [mm²] = 2 x 2,5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
450
400
350
300
250
200
150
100
50
0
A = 6 mm²
A = 2,5 mm²
A = 1,5 mm²
A = 2 x 2,5 mm²
Sum of drive rated currents I / A