5-5
Function group 1
LED
display
Address
for
commu
nication
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
F30
A21E
[V/F
pattern]
0 ~ 2
0
{Linear}
0
X
7-17
1
{Square}
7-17
2
{User V/F}
7-18
F31
1)
A21F
[User V/F
frequency
1]
0 ~ 400
[Hz]
It is used only when V/F pattern is set to
2(User V/F)
It cannot be set above F21 [Max
frequency].
The value of voltage is set in percent of
H70 [Motor rated voltage].
The values of the lower-numbered
parameters cannot be set above those of
higher-numbered.
15.00
X
7-18
F32
A220
[User V/F
voltage 1]
0 ~ 100
[%]
25
X
F33
A221
[User V/F
frequency
2]
0 ~ 400
[Hz]
30.00
X
F34
A222
[User V/F
voltage 2]
0 ~ 100
[%]
50
X
F35
A223
[User V/F
frequency
3]
0 ~ 400
[Hz]
45.00
X
F36
A224
[User V/F
voltage 3]
0 ~ 100
[%]
75
X
F37
A225
[User V/F
frequency
4]
0 ~ 400
[Hz]
60.00
X
F38
A226
[User V/F
voltage 4]
0 ~ 100
[%]
100
X
F39
A227
[Output
voltage
adjustment
]
40 ~ 110
[%]
This parameter adjusts the amount of
output voltage.
The set value is the percentage of input
voltage.
100
X
7-18
F40
A228
[Energy-
saving
level]
0 ~ 30
[%]
This parameter decreases output voltage
according to load status.
0
0
8-17
F50
A232
[Electronic
thermal
select]
0 ~ 1
This parameter is activated when the
motor is overheated (time-inverse).
0
0
10-1
1)
: Set F30 to 2(User V/F) to display this parameter.
For Service Call 800-848-2504
For Service Call 800-848-2504

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ig5a and is the answer not in the manual?

LSIS sv-ig5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ig5a
CategoryInverter
LanguageEnglish

Related product manuals