Chapter 3 Analog Output Module (XBF-DV04A, XBF-DC04A, XBF-DC04B)
3 - 23
XBF-DC04B
Address
(Dec)
Description
Details
Remarks
0
Set up the run channel
Bit On(1): Run
Bit Off(0): Stop
Read/Write
available
1
Set up the output voltage range
Bit (00): 4 ~ 20mA
Bit (01): 0 ~ 20mA
2
Set up the input data type
Bit (00): 0 ~ 4000
Bit (01): -2000 ~ 2000
Bit (10): 0 ~ 1200
Bit (11): 0 ~ 1000
3
Set up the output type of CH0
0: outputs the previous value
1: outputs the min. value of output range
2: outputs the mid. value of output range
3: outputs the max. value of output range
4
Set up the output type of CH1
5
Set up the output type of CH2
6
Set up the output type of CH3
11
CH0 setting error
Error code
Read
available
12
CH1 setting error
13
CH2 setting error
14
CH3 setting error
(1) Setting up the run channel
If the run channel is not specified, all the channels will be set to Stop.
(2) Setting up the output voltage/current range
The range of analog output voltage is DC 0 ~ 10V and analog output current is DC 4 ~ 20mA,
DC 0 ~ 20mA.
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
-
C
H
3
C
H
2
C
H
1
C
H
0
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
-
CH 3
CH 2
CH 1
CH 0
Run channel (bit)
1: Run
0: Stop
Output range (bit)
00: 0 ~ 10V(4 ~ 20mA)
01: 0 ~ 20mA
Address “0”