XGB Analog edition manual 
 
 
6.4.2   Output Characteristics 
The graph below shows the data conversion characteristics by output range. 
Digital 
input
Analog 
output
Practical analog output 
range
     
Offset 
value
 
Gain 
value
DC 1 ~ 5 V
DC 0 ~ 5 V
DC 0 ~ 10 V
DC 4 ~ 20 mA
1 V 5 V3 V
0 V 2.5 V 5 V
0 V 5 V 10 V
4 mA 12 mA 20 mA
DC 0 ~ 20 mA 0 mA 10 mA 20 mA
0
1000
2000
3000
4000
4047
-48
-2000
-1000
0
1000
2000
2047
-2048
0
250
500
750
1000
1011
-12
 
  (1) DC 4 ~ 20mA Range Output 
Analog Output Current (mA) 
Unsigned Value 
(0 ~ 4000) 
0 less  0  1000  2000  3000  4000  4000 over 
Signed Value 
(-2000 ~ 2000) 
-2000 less 
-1000  0  1000  2000  2000 over 
Precise Value 
(400 ~ 2000) 
400 less  400  800  1200  1600  2000  2000 over 
Percentile 
Value(0 ~ 1000) 
0 less  0  250  500  750  1000  1000 over 
 
(2) DC 0 ~ 20mA Range Output 
Digital Input 
Analog Output Current (mA) 
Unsigned Value 
(0 ~ 4000) 
0 less 
0  1000  2000  3000  4000 
4000 over
Signed Value 
(-2000 ~ 2000) 
-2000 less
-2000  -1000  0  1000  2000 
2000 over
Precise Value 
0 less 
0  500  1000  1500  2000 
2000 over
Percentile 
0 less 
0  250  500  750  1000 
1000 over
 
6 - 8