XGB Analog edition manual
10.4.2 Output characteristic
Data conversion characteristic per output range is as follows.
Digital
input
0
1000
2000
3000
4000
4047
-2000
-1000
0
1000
2000
2047
0
250
500
750
1000
1011
DC 4 ~ 20 mA
DC 0 ~ 20 mA
DC 0 ~ 10 V
4 mA 20 mA12 mA
0 mA
0 V 5 V 10 V
Analog
output
Analog output practical
range
Offset
Gain
20 mA10 mA
(1) DC 4~20mA range output
Digital input
range
Analog output current (mA)
4mA or
4 8 12 16 20
Over
Unsigned value
(0 ~ 4000)
0 or less 0 1000 2000 3000 4000
Signed value
(-2000 ~ 2000)
-2000 -1000 0 1000 2000
Precise value
400 800 1200 1600 2000
Percentile value
0 or less 0 250 500 750 1000
(2) DC 0 ~ 20mA range output
Digital input
range
Analog output current (mA)
0mA or
0 5 10 15 20
Over
Unsigned value
(0 ~ 4000)
0 or less 0 1000 2000 3000 4000
Signed value
(-2000 ~ 2000)
-2000 -1000 0 1000 2000 Over 200
0 or less 0 500 1000 1500 2000
Percentile value
0 or less 0 250 500 750 1000
10 - 8