The individual input / selection fields and checkboxes can vary, depending on the device, type and selected
settings.
Connect to Server
on
Selection field for when and under which conditions the device should connect to the
server.
Dialout/Function But-
ton
Pressing the "Dialout" or "Function" button on the appropri-
ate device establishes a connection to the server.
Always A connection is established as soon as the device is
switched on and ready for operation.
SMS The command to establish a connection is sent to the de-
vice via a text message.
Start when Input 1 is
active (1 signal)
Depending on the device and type, the connection can be
controlled using one or more digital inputs.
Start when Input 1 is
active (1 signal), stop
on 0 signal
Depending on the device and type, the connection can be
controlled using one or more digital inputs.
Ignore traffic on
LAN
If this check box is activated, no connection that differs from the setting under
"Connect to server on" can be established. For example, a component connected to
the LAN uses the device (router) as a gateway.
Ignore traffic from
internal services
If this check box is activated, no connection that differs from the setting under
"Connect to server on" can be established. For example, if an e-mail is to be sent by
the device (router) or an automatic time synchronization is to be executed.
Disconnect after
inactivity time of
[sec]
When the preset time has elapsed (timeout), the connection between the server and
device is disconnected.
Connect to send
Log Data
The device connects to the server to send log data, irrespective of the selection of
when and under which conditions the device is to establish a connection (with the ex-
ception of the selection "Always"). The connection is disconnected after the preset
timeout.
Log Data Interval Selection field for the interval (1 hr., 2 hrs., 4 hrs., 8 hrs., 12 hrs., 24 hrs.) of the data
logged during this period of time.
Time to Send Log
Data
Initial time, from which the log data is sent in the preset interval.