62Z8038A
OUTP:
Latching reset
[ 040 088 ]
OUTP:
State K xxx
[ ZZZ ZZZ ]
OUTP:
Outp. relays blocked
[ 021 015 ]
OUTP:
Oper. mode K xxx
[ xxx xxx ]
1: ES updating
2: ES manual reset
1
2
3: ES reset (fault)
3
4
5
6
4: ES reset (syst.dist)
5: NE updating
6: NE manual reset
-K xxx
OUTP:
Fct.assignment K xxx
[ yyy yyy ]
OUTP:
Outp.rel.block USER
[ 021 014 ]
0
1
0: No
1: Yes
OUTP:
Reset latch. USER
[ 021 009 ]
0
1
0: don't execute
1: execute
1
100 ms
Selected signal
Signal 1
Signal 2
Signal 3
Signal n
SFMON:
Hardware fault
304 950
OUTP:
Block outp.rel. EXT
[ 040 014 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]
FT_RC:
Record. in progress
[ 035 000 ]
FT_RC:
System disturb. runn
[ 035 004 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
OUTP:
Reset latch. EXT
[ 040 015 ]
1
S
R
1
1
1
MAIN:
General reset EXT
[ 005 255 ]
Fig. 3-29: Configuration, setting the operating mode, and blocking the output relays.
Testing the Output Relays
For testing purposes, the user can select an output relay and trigger it via a
setting parameter. Therefore the P631 must be switched to “off-line”. Triggering
persists for the duration of the set hold time.
3 Operation
P631
P631/EN M/R-11-C // P631-310-650 3-45