2.4 Environmental Conditions
Temperatures
Recommended temperature range
-5°C to +55°C [+23°F to +131°F].
Limit temperature range
Operation: -25°C to +55°C [-13°F to +131°F].
Storage and transport: -25°C to +70°C [-13°F to +158°F].
Ambient Humidity Range
75 % relative humidity (annual mean).
56 days at 95 % relative humidity and 40°C [104°F].
Condensation not permitted.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.