2.12 Power Supply
Nominal auxiliary voltage V
A,nom
●
24 to 60 V DC or 60 to 250 V DC and 100 to 230 V AC (ordering option).
Operating range for direct voltage
●
0.8 to 1.1 V
A,nom
with a residual ripple of up to 12 % V
A,nom
.
Operating range for alternating voltage
●
0.9 to 1.1 V
A,nom
.
Nominal burden
●
… where V
A
= 220 V DC and with maximum module configuration
■
40 TE case, relays de-energized/energized: approx. 12.6 W / 34.1 W
Start-up peak current
●
< 3 A for duration of 0.25 ms
Stored energy time
●
≥ 50 ms for interruption of V
A
≥ 220 V DC (upper range supply)
●
≥ 50 ms for interruption of V
A
≥ 60 V DC (lower range supply)