EasyManua.ls Logo

Micom P631 - Monitoring Condition

Micom P631
638 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64Z5301A
MAIN:
Protection active
306 001
CTS:
Blocking EXT
[ 036 160 ]
DIFF:
Harm.block 1 trigg.
[ 041 118 ]
DIFF:
Harm.block 2 trigg.
[ 041 119 ]
DIFF:
Harm.block 3 trigg.
[ 041 120 ]
MAIN:
Gen. trip signal
[ 036 251 ]
CTS:
Enabled
[ 036 080 ]
CTS:
blocked
460 400
1
1
Fig. 3-117: Blocking of current transformer supervision
3.25.4 Monitoring Condition
If CTS is ready, it will monitor the positive- and negative-sequence currents from
both transformer ends (a, b).
A CT fault is detected when the following conditions are simultaneously present:
The positive-sequence current exceeds the set threshold I
pos>
in both
winding ends. This means that CTS can operate only if a minimum load
current is present in the protected object.
The negative- to positive-sequence current ratio exceeds a high set
threshold value I
neg
/I
pos>>
in a single winding end.
In the other end, the negative- to positive-sequence current ratio is smaller
than the low set threshold value I
neg
/I
pos>
, or no significant current is
present (i.e. the positive-sequence current is lower than the I
pos>
threshold).
In such a case, there is a fault in the secondary circuit of the CT at the
transformer end where a high negative-sequence current is present.
Because this function uses negative-sequence currents, it can only detect
unbalanced CT faults. In practice, this does not present a problem as the
occurrence of a three-pole CT fault is very unlikely.
P631
3 Operation
3-152 P631/EN M/R-11-C // P631-310-650

Table of Contents

Related product manuals