9.9 Controls
9.9.1 Control Objects
Parameter
Control Object
Parameters
ctlModel
To control external devices the following operating modes can be set:
●
Status only (manually operated switching device)
●
Direct control with enhanced security (direct command issue with
extended monitoring of command effecting)
●
SBO (Select before operate) with enhanced security (switching device
selection procedure with extended monitoring of command effecting)
sboTimeout
Return time period after selection without issuing a command.
9.9.2 Uniqueness of Control
Parameter
Source Network
Parameters
Multicast MAC Address
Virtual MAC address used as a receive filter; preset.
Application ID (hex)
ID-number of the GOOSE.
9 IEC 61850 Settings via IED Configurator
P631
P631/EN M/R-11-C // P631-310-650 9-13